    Overview

    The HNPJF series GIS partial discharge online monitoring system adopts the UHF detection technology. The system uses the integrated modular design to integrate the signal acquisition unit, signal processing, A/D conversion, interference filtering, data processing and discharge quantity display, etc. in the station-end monitoring module. Each station-end monitoring module can run independently and records data respectively. Through a data communication bus, the data of several in-station monitoring modules is transmitted to the background analysis system for unified management and analysis. Through the Internet for remote transmission and real-time monitoring, the intensity and density of partial discharge signals can be analyzed online in real time. The real-time monitoring and analysis of the partial discharge tendency and the evaluation of the discharge degree are performed to avoid major accidents.

    Main Features

    l With the UHF method for monitoring, the system has strong anti-interference capability and high sensitivity (no less than 5pC); the system can operate reliably and stably in all kinds of bad weather and under any environment such as strong electromagnetic interference, radio interference and mechanical vibration.

    l The system can realize continuous real-time measurement of discharge pulse repetition times, amplitude and phase, data statistics, and drawing of 2D (φ-Q, φ-n and Q-n) and 3D spectrograms (φ-Q-n). The system can achieve accurate locating diagnosis of partial discharge fault points through information mode identification and fault type diagnosis;

    l The system can realize calculation and analysis of the historical development trend of the maximum discharge amplitude and discharge times of the partial discharge of the tested equipment, and evaluate the internal insulation status of GIS. The system can ensure the safety of the power system and provide basis for status inspection and repair of the equipment; and can provide reliable technical data for equipment adjustment evaluation and predictive maintenance.

    l The system can realize network remote diagnosis technology and automatic continuous remote transmission of data, etc.

    l With complete functions, the system has accident recalling, strong data analysis and processing, historical trend analysis and rich display functions, and its overall functional technology has reached the international leading level.

    Technical Parameters

    FAGN


    UHF sensor

    Monitoring frequency band

    300MHz~3000MHz

    Sensitivity

    <5PC (external),<1PC (built-in)

    Amplification gain

    65dB

    Dynamic range

    -80~-20dBm

    Impedance

    50Ω

    Interface

    N-type

    Installation position

    Outside of basin-type insulator (external), end cover (internal)

    Dynamic monitoring range

    -80dBm~-20dBm

    Partial discharge IED

    Working voltage

    220V/50HZ

    Chassis dimensions

    428*177*500 (mm) or can be customized according to customer requirements

    Signal interface

    1-way RJ45, 16-way N-type interface or can be customized according to customer requirements

    Background processing system

    Server

    Advantech 510 series industrial computer + Dell 19 monitor

    Measurement content

    Discharge amplitude (Q), discharge phase (φ) and discharge times (N)

    Customer software

    Remote control software, and remote monitoring and analysis software

    Communication protocol

    RS485, TCP/IP and IEC61850